Seitenansicht 101
102 ,VRO DWLQJ&DXVHV
Temperature
is over limit
Critical none none Critical
Temp is
>54.5º C
A fan is faulty. Check status and
correct.
Airflow is obstructed; vents are
blocked.
One or more slots are empty.
Power supply is faulty. Check status
and correct.
Room temperature is too high. If
ambient temperature cannot be
reduced in a reasonable time, turn
off product to prevent shortened life.
Temperature sensor is faulty.
Compare temperature reported by
peer LCC.
Major
Warning
none none Non-
critical
Temp is
>36º C
7HPSHUDWXUHVHQVRUVDUHRQWKH/&&
DQGDUHLQGHSHQGHQWRISRZHUVXSSOLHV
,QYHVWLJDWHWHPSHUDWXUHZDUQLQJV
LPPHGLDWHO\EHIRUHSRZHUVXSSOLHVVHQVH
FULWLFDOWHPSHUDWXUHDQGWXUQRII
Temperature
is under limit
Critical none none Critical
Temp s
<9.5º C
Room temperature is too low.
Temperature sensor is faulty.
Compare temperature reported by
peer LCC.
Major
Warning
none none Non-
critical
Temps
<15.5º C
Voltage is
over limit
Critical none none Critical Power supply is faulty. Check status
and correct.
Major
Warning
none none Non-
critical
Voltage is
under limit
Critical none none Critical Either power supply is faulty. Check
status and correct.
Major
Warning
none none Non-
critical
7DEOH 7URXEOHVKRRWLQJ7DEOHFRQWªG
Problem
Description
HWEvent
Category
LED
State
Status
Probable Cause/SolutionSAM STM
Seitenansicht 101